    Inflatable Air Blower are you known?

    Date: 2014-10-13   Click: 1447 Times

    (1) "Inflatable Air Blower" main control parameters temperature, air flow, total pressure, efficiency, noise, electrical power, speed and shaft power of choice.
    (2) In the medium temperature not higher than 85 ℃ conditions for higher exhaust fan should be a long run.
    (3) exhaust fan should ensure that: When the transmission medium temperature at 280 ℃ continuous working time 30min, still continuous medium temperature cooling to room temperature during normal operation.
    (4) In the rated speed, in the work area, measuring ventilator pressure curve and the curve given in the specification should meet the requirements: Axial exhaust fan in the provisions corresponding to ± 5% deviation of the pressure value.
    (5) "Inflatable Air Blower" centrifugal expelling fan predetermined flow rate, ± 5% of the pressure value corresponding to the deviation.
    (6) an indication of the operating point A sound level exhaust fan noise limits should be consistent with JB / T8690-1998 consistent.
    (7) exhaust fan can be ordinary or special steel centrifugal exhaust fans axial fans. According to "fire protection design of tall buildings" in the provisions of fan specifications. The minimum air volume fan 7200 m / h, not more than 60,000 m / h, the maximum amount of wind (refers to the maximum volume of air smoke partitions).
    (8) the exhaust air flow should increase the fan flow value of not less than 10% to 20% of the surplus amount.
    (9) pressure ventilation exhaust system pressure should calculate the most unfavorable loop and ensure that the value of the residual pressure in the stairwell 40? 50Pa's. In front of the room residual pressure, common room, fire elevator room, refuge floors worth 25? 30PA's.
    (10) fire exhaust fan should be consistent with the current standard JB / T10281-2001 comply "exhaust fan fire technical conditions."
    (11) "Inflatable Air Blower" exhaust system should be set separately. Exhaust fans must be in the same location or upper smoke zone.

    Back to: Industry news

    +86-0769-83660708

    Home Product News Contact

    主站蜘蛛池模板: 免费一级黄色大片| 日本www.色| 亚洲精品美女久久7777777| 美女扒开超粉嫩的尿口视频| 在线观看欧美日韩| 一区五十路在线中出| 无码办公室丝袜OL中文字幕| 久久精品无码免费不卡| 欧美孕妇乱大交xxxx| 亚洲精品乱码久久久久久蜜桃 | 为什么高圆圆被称为炮架| 日韩精品无码免费一区二区三区| 亚洲国产精品福利片在线观看| 波多野结衣妻奴| 伦理eeuss| 男的把j放进女人下面视频免费| 国产成人精品日本亚洲| 三上悠亚在线网站| 国产精品色内内在线播放| 99久久精品国产片久人| 女儿国交易二手私人衣物app| 久久无码精品一区二区三区| 欧美乱子伦videos| 亚洲性生活网站| 欧美群交在线播放1| 亚洲精品无码久久久久| 狠狠热免费视频| 国产zzjjzzjj视频全免费| 青青草视频ios| 国产在线视频一区二区三区98| 国产精品亚洲综合五月天| 国产爆乳无码一区二区麻豆| youjizz护士| 天天爱添天天爱添天天爱添| 一区二区三区www| 小说区亚洲自拍另类| 一级毛片成人免费看a| 日本黄大片在线观看| 久久精品国产亚洲精品2020| 日韩美女va毛片在线播放| 亚洲av人无码综合在线观看|